Design and supply of multiple Eurovent Certified Air Handling Units
Normal mode: Technical rooms – Supply air 5730m³/h. Extract 5080m³/h
Emergency mode: Data Hall Supply air 11680m³/h. Extract 10700m³/h
Includes:
• Weatherproof execution, panels powder coated inside + outside
• Cabinet installed and pre-wired in section on top deck of the unit
• Smoke detectors IP54 plus UG-Cover-75, (including 5m of cable for each sensor)
• Fire alarms inputs for BMS
• Condair EL 24 for 24kg/hr steam generation (cabinet installed in section on top deck of the unit)
• Unit delivered in 1 piece (additional 120mm high baseframe needed which is noted but not shown on the drawing)
• Standard white PVC U-traps included
• Duct mounted dampers and actuators – 800x510mm, on/off control
• Access and pipe connections on left hand side looking in direction of supply air flow
• All fans/motor are the same size Ebmpapst EC 560 with IE4 5kW EC motor
Normal mode: Data Hall – Supply air 11680m³/h. Extract 10700m³/h
Emergency mode: actived when this unit (VK.01.02) fails
Includes:
• Indoor execution, panels powder coated inside + outside
• ARC TECH LEVEL II control system
• ARC Modbus RTU communication card
• 24V smoke detectors, (including 5m of cable for each sensor)
• Fire alarms inputs for BMS
• Condair EL 24 for 24kg/hr steam generation
• Duct mounted dampers (supplied loose) and actuators (supplied loose) – 1000x675mm, on/off control
• Access and pipe connections on right hand side looking in direction of supply air flow.
• All fans/motor are the same size Ebmpapst EC 560 with IE4 5kW EC motor